Daikin Sensing Technology

Dual Sensors

Dual Sensors and individual airflow direction control automatically provide optimal control of airflow.

Infrared Presence Sensor

The sensor detects the presence of people in each of 4 areas.

Ceiling Height 2.7m 3.5m 4.0m
Diameter range (diameter)*3 Approx. 8.5m Approx. 11.5m Approx. 13.5m
Infrared Floor Sensor

The sensor detects the floor temperature and automatically adjusts operation of the indoor unit to reduce the temperature difference between the ceiling and the floor.

Ceiling Height 2.7m 3.5m 4.0m
Diameter range (diameter)*4 Approx. 11m Approx. 14m Approx. 16m

Auto Airflow Functions

Individual Airflow Direction Control

Airflow direction can be individually adjusted for each discharge outlet to deliver optimal air distribution.

Individual Airflow Settings

  • No Individual setting (Auto airflow)
  • Position 0 (Highest point)
  • Position 1
  • Position 2
  • Position 3
  • Position 4 (Lowest point)
  • Swing

When individual airflow is selected, airflow direction can be adjusted to room layout.

Circulation Airflow Evenly Distributes Cool Air

Conventional airflow had areas that were either too cool or not cool enough.

Circulation airflow cools the entire room to deliver comfort that never feels cold.

Configurations of Circulation Airflow (Cooling)

Technology to Improve Energy Efficiency

Outdoor Unit

The cassette type 125 class outdoor unit uses a larger and more efficient compressor than the current model.

The micro channel heat exchanger is getting wider and more efficient.

Indoor Unit (Cassette type)

The cassette type 100/125 class uses a higher integrated heat exchanger to improve efficiency.

Durability

Micro Channel Heat Exchanger

Micro channel technology utilises superior heat transfer benefits of aluminum to create a more efficient air conditioner. With a new resistance corrosion aluminum alloy, the Daikin micro channel heat exchanger becomes highly durable. A salt spray test has been conducted to demonstrate the corrosion-resistant capability of our products in corrosive environments for a certain period of time.

After undergoing an intensive test, the Daikin micro channel heat exchanger is able to maintain its shape without corrosion, which strongly confirms its durability in a highly corrosive environment.

Enhanced Protection Against Dissimilar Metal Corrosion

In many Asian regions, corrosive substances such as iron, chlorine, nitrogen oxides, and sulfur oxides are known to accelerate refrigerant leakage due to dissimilar metal corrosion. To address this, the new RZF-D/DA models in the Premium series apply a zinc spray coating to the multi-hole tubs of MCHX (Micro Channel Heat Exchanger).

This treatment significantly improves resistance to corrosion between dissimilar metals, enhancing durability in environments with high corrosion risk.

The design is based on the proven technology used in existing Premium (RZF) models, ensuring reliable performance even under harsh outdoor conditions.

Enhanced PCB Protection Against Gecko Entering

In many Asian regions, small geckos and foreign objects are major cause of outdoor unit PCB failures. Daikin has reinforced its PCB design with preventive measures to ensure long-lasting performance and reliability.

RZF50-71DVMG, RZF71DAVMG (Small Casing)

The control box is fully enclosed with metal sheet covers, preventing small animals and debris from entering.

RZF100/125DVMG, RZF100-140DAVMG (Medium to Large Casing)

A resin cover is installed from the side to the back of the PCB. The gap between the PCB and the resin cover is minimized to just 1 mm, effectively deterring geckos without compromising heat dissipation.

Automatic Protection Against Low Voltage

In AM and PM peak electricity consumption periods, supply may fluctuate. Built-in low-voltage protection will automatically cut operations. When normal voltage is restored, operation will resume as before.

Coated Printed Circuit Boards

Coated circuit boards prevent problems by humidity and airborne dust. It also protects against salt contained in sea breezes. Both sides of the PCB in outdoor units are coated.

Reuse of Existing Piping

Benefit 1 : Simplified Installation Reduces Replacement Time and Cost

Benefit 2 : You Can Increase Cooling Capacity and Achieve Higher Energy Efficiency
Upgrade to an air conditioner with the latest technology for greater comfort and energy efficiency.

Technology
Advanced technology, including the use of corrosion resistant electronic expansion valves, acid neutralisers and improved compressor reliability, enables the re-use of existing piping* without the need of pipe flushing for a simplified replacement process.

Specifications

Ceiling Mounted Cassette Type (Round Flow)

Comfortable Airflow Travels Throughout the Room

50 60 71 100 125 100 125 140
Model
Name
Indoor unit FCQ50LUV1 FCQ60LUV1 FCQ71LUV1 FCQ100KAVEA FCQ125KAVEA FCQ100KAVEA FCQ125KAVEA FCQ140KAVEA
Outdoor unit RZR50LWM RZR60LWM RZR71LWMG RZR100MVMG RZR125MVMG RZR100MYM RZR125MYM RZR140MYM
Power supply Outdoor unit 1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz
Cooling capacity1,2 kW
Btu/h
5.0 (2.3-5.6)
17,100 (7,900-19,100)
6.0 (2.6-6.3)
20,500 (8,900-21,500)
7.1 (3.2-8.0)
24,200 (10,900-27,300)
9.5 (4.5-11.2)
32,400 (15,400-38,200)
10.8 (5.4-14.0)
36,900 (18,400-47,800)
10.0 (5.0-11.2)
34,100 (17,100-38,200)
12.5 (5.7-14.0)
42,700 (19,500-47,800)
14.0 (6.2-15.4)
47,800 (21,200-52,600)
Power consumption Cooling1 kW 1.03 1.40 1.80 2.51 3.22 2.78 4.31 5.62
COP W/W 4.85 4.29 3.78 3.79 3.35 3.60 2.90 2.49
Indoor
unit
Colour Decoration panel Fresh white
Airflow rate (H/M/L) m³/min 21/-/13.5 32/26/20 33/28/22.5 32/26/20 33/28/22.5
Sound level (H/H/H/M/L)3 dB(A) [-/-35/-28] (43/37.5/-32) (44/39/-34) [-/43/37.5/32] [-/44/39/34] [-/44/40/36]
Dimensions
(H×W×D)
Unit mm 256×840×840 298×840×840
Decoration panel mm 50×950×950
Machine
weight
Unit kg 21 24
Decoration panel kg 5.5
Certified Operation range Cooling °CWB 14 to 25
Outdoor
unit
Colour Ivory white
Compressor Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.12 1.35 1.76 2.03 2.03 1.92 1.92
Refrigerant charge (R-410A) kg 1.6
(Charged for 30 m)
1.9
(Charged for 30 m)
1.9
(Charged for 30 m)
1.9
(Charged for 30 m)
Sound level3 Cooling dB(A) 48 49 52 49 52 54
Night quiet mode dB(A) 44 44 45
Dimensions (H×W×D) mm 595×845×300 990×940×320 990×940×320
Machine weight kg 43 65 73
Certified Operation range Cooling °CDB 21 to 46
Piping
connections
Liquid (Flare) mm ϕ 9.5
Gas (Flare) mm ϕ 15.9
Drain Indoor unit mm VP25 (I.D ϕ 25×O.D ϕ 32)
Outdoor unit mm ϕ 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping

Note : 1Rated cooling capacities are based on the following conditions:
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB.
Equiv. refrigeration piping, 7.5 m (horizontal)
2Capacities are net, including a deduction for cooling for indoor fan motor heat.
3Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.

Duct Connection Middle Static Pressure Type

Thinner Design Allows Greater Installation Flexibility

50 60 71 100 125
Model
Name
Indoor unit FBQ50EVE FBQ60EVE FBQ71EVE FBQ100EVE FBQ125EVE
Outdoor unit RZR50LVM RZR60LVM RZR71LVMG RZR100MVMG RZR125MVMG
Power supply Indoor unit 1 Phase, 220–240 V, 50 Hz
Outdoor unit
Cooling capacity1,2
Rated (Min. – Max.)
kW
Btu/h
5.0 [2.3–5.6]
17,100 [7,900–19,100]
6.0 [2.6–6.3]
20,500 [8,900–21,500]
7.1 [3.2–8.0]
24,200 [10,900–27,300]
9.5 [4.5–11.2]
32,400 [15,400–38,200]
10.8 [5.4–14.0]
36,900 [18,400–47,800]
Power consumption Cooling1 kW 1.39 1.69 2.22 2.51 3.22
COP W/W 3.60 3.56 3.20 3.79 3.35
Indoor
unit
Fan Airflow rate (H/M/L) m³/min 18/15/12.5 23/19.5/16 32/27/22.5 36/30.5/25
External static pressure3 Pa Rated 50 (50–150)
Sound pressure level (H/M/L)4 dB(A) 35/33/31 38/35/33 38/35.5/33 40/37.5/35
Dimensions (H×W×D) mm 245×1,000×800 245×1,400×800
Machine weight (indoor) kg 37 47
Outdoor
unit
Sound pressure
level4
Cooling dB(A) 48 49 52
Night quiet mode dB(A) 44 45
Dimensions (H×W×D) mm 595×845×300 990×940×320
Machine weight (outdoor) kg 43 65
Piping
connection
Liquid mm φ 9.5 (Flare)
Gas mm φ 15.9 (Flare)
Drain Indoor unit mm VP25 (I.D φ25×O.D φ32)
Outdoor unit mm φ 26 (Hole)
Max interunit piping length mm 50 (Equivalent length 70m)
Heat insulation Both liquid and gas piping
100 125 140
Model
Name
Indoor unit FBQ100EVE FBQ125EVE FBQ140EVE
Outdoor unit RZR100MYM RZR125MYM RZR140MYM
Power supply Indoor unit 1 Phase, 220–240 V, 50 Hz
Outdoor unit 3 Phase, 380–415 V, 50 Hz
Cooling capacity1,2
Rated (Min. – Max.)
kW
Btu/h
10.0 [5.0–11.2]
34,100 [17,100–38,200]
12.5 [5.7–14.0]
42,700 [19,500–47,800]
14.0 [6.2–15.4]
47,800 [21,200–52,600]
Power consumption Cooling1 kW 2.82 4.58 5.85
COP W/W 3.55 2.73 2.39
Indoor
unit
Fan Airflow rate (H/M/L) m³/min 38/35.5/33 36/30.5/25
External static pressure3 Pa Rated 50 (50–150)
Sound pressure level (H/M/L)4 dB(A) 40/37.5/35 40/37.5/35
Dimensions (H×W×D) mm 245×1,400×800
Machine weight (indoor) kg 47
Outdoor
unit
Sound pressure
level4
Cooling dB(A) 49 52 54
Night quiet mode dB(A) 45
Dimensions (H×W×D) mm 990×940×320
Machine weight (outdoor) kg 73
Piping
connection
Liquid mm φ 9.5 (Flare)
Gas mm φ 15.9 (Flare)
Drain Indoor unit mm VP25 (I.D φ25×O.D φ32)
Outdoor unit mm φ 26 (Hole)
Max interunit piping length m 50 (Equivalent length 70m)
Heat insulation Both liquid and gas piping

Note: 1Rated cooling capacities are based on the following conditions:
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB.
Equiv. refrigeration piping, 7.5 m (horizontal)

2Capacities are net, including a deduction for cooling for indoor fan motor heat.

3External static pressure is changeable in 11 stages by remote controller.

4Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.

5Air filter is not standard accessory, but please mount it in the dust system of the suction
side.
Select its duct collection efficiency (gravity method) 50% or more.

Ceiling Suspended Type

Cassette Air Conditioner with 360 degrees Uniform Airflow sets the Standard

50 60 71
Model
Name
Indoor unit FHQ50BW1G FHQ60BW1G FHQ71BW1B
Outdoor unit RZR50LVM RZR60LVM RZR71LVM
Power supply Outdoor unit 1 Phase, 220–240 V, 50 Hz
Cooling capacity1,2
Rated (Min. – Max.)
5.0 (2.3–5.6)
17,100 (7,900–19,100)
6.0 (2.6–6.3)
20,500 (8,900–21,500)
7.1 (3.2–8.0)
24,200 (10,900–27,300)
Power consumption Cooling1 kW 1.39 1.69 2.50
COP W/W 3.60 3.56 2.84
Indoor
unit
Colour White
Airflow rate (H/L) m³/min 17/-/14
Sound level (H/L)2 dB(A) 39/-/35
Dimensions (H×W×D) mm 195×1,160×680
Machine weight kg 27
Certified operation range °CWB 14 to 25
Outdoor
unit
Colour Ivory white
Compressor Type Hermetically sealed swing type
Motor output kW 1.12 1.35 1.76
Refrigerant charge (R-410A) kg 1.6 (Charged for 30 m)
Sound level3 Cooling dB(A) 48
Night quiet mode dB(A) 44
Dimensions (H×W×D) mm 595×845×300
Machine weight kg 43
Certified operation range °CDB 10 to 46
Piping
connections
Liquid (Flare) mm φ 9.5
Gas (Flare) mm φ 15.9
Drain Indoor unit mm VP20 (I.D φ20×O.D φ26)
Outdoor unit mm φ 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference 30
Heat insulation Both liquid and gas piping
100 125 100 125 140
Model
Name
Indoor unit FHQ100BV1B FHQ125BV1B FHQ100DAVMA FHQ125DAVMA FHQ140DAVMA
Outdoor unit RZR100LVM RZR125LVM RZR100MYM RZR125MYM RZR140MYM
Power supply Outdoor unit 1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz
Cooling capacity1,2
Rated (Min. – Max.)
10.0 (5.0–11.2)
34,100 (17,100–38,214)
12.5 (5.7–14.0)
42,700 (19,500–47,800)
10.0 (5.0–11.2)
34,100 (17,100–38,200)
12.5 (5.7–14.0)
42,700 (19,500–47,800)
14.0 (6.2–15.4)
47,800 (21,200–52,600)
Power consumption Cooling1 kW 3.51 4.55 3.03 4.42 5.55
COP W/W 2.85 2.75 3.3 2.83 2.52
Indoor
unit
Colour white Light Ivory
Airflow rate (H/M/L) m³/min 24/-/-/20 30/-/25 28/24/20 31/27/23 34/29/24
Sound level (H/M/L)2 dB(A) 42/-/37 44/-/39 42/38/34 44/41/37 46/42/38
Dimensions (H×W×D) mm 195×1,400×680 195×1,590×680 235×1,590×690
Machine weight kg 32 35 38
Certified operation range °CWB 14 to 25
Outdoor
unit
Colour Ivory white
Compressor Type Hermetically sealed swing type Hermetically sealed scroll type Hermetically sealed swing type
Motor output kW 2.03 2.6 1.92
Refrigerant charge (R-410A) kg 2.7
(Charged for 30 m)
3.15
(Charged for 30 m)
1.9
(Charged for 30 m)
Sound level3 Cooling dB(A) 49 50 49 52 54
Night quiet mode dB(A) 45 46
Dimensions (H×W×D) mm 990×940×320 1,170×900×320 990×940×320
Machine weight kg 78 97 73
Certified operation range °CDB 21 to 46
Piping
connections
Liquid (Flare) mm φ 9.5
Gas (Flare) mm φ 15.9
Drain Indoor unit mm VP20 (I.D φ20×O.D φ26)
Outdoor unit mm φ 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference 30
Heat insulation Both liquid and gas piping

Note : 1Rated cooling capacities are based on the following conditions:
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB.
Equiv. refrigeration piping, 7.5 m (horizontal).

2Capacities are net, including a deduction for cooling for indoor fan motor heat.

3Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.

Wall Mounted Type

Compact Design and Easy Installation

71 100 100
Model
Name
Indoor unit FAQ71CVEA FAQ100CVEA FAQ100CVEA
Outdoor unit RZR71LVM RZR100LVVM RZR100MYM
Power supply Outdoor unit 1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz
Cooling capacity1,2
Rated (Min. – Max.)
kW
Btu/h
7.1 (3.2-8.0)
24,200 (10,900-27,300)
10.0 (5.0-11.2)
34,100 (17,100-38,200)
Power consumption Cooling1 kW 2.19 3.37
COP W/W 3.24 2.97
Indoor
unit
Colour Fresh white
Airflow rate (H/M/L) m³/min 18/16/14 26/23/19
Sound level (H/M/L)3 dB(A) 45/42/40 49/45/41
Dimensions (H×W×D) mm 290×1,050×238 340×1,200×240
Machine weight kg 13 17
Certified Operation range °CWB 14 to 25
Outdoor
unit
Colour Ivory white
Compressor Type Hermetically sealed swing type
Motor output kW 1.76 2.03 1.92
Refrigerant charge (R-410A) kg 1.6 (Charged for 30 m) 3.35 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound level3 Cooling dB(A) 48 49
Night quiet mode dB(A) 44 45
Dimensions (H×W×D) mm 595×845×300 900×940×320
Machine weight kg 43 78 73
Certified Operation range °CDB 21 to 46
Piping
connections
Liquid (Flare) mm φ 9.5
Gas (Flare) mm φ 15.9
Drain Indoor unit mm VP13 (I.D φ 13 × O.D φ 18)
Outdoor unit mm φ 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70m)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping

Note :

1Rated cooling capacities are based on the following conditions:
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB.
Equiv. refrigeration piping, 7.5 m (horizontal).

2Capacities are net, including a deduction for cooling for indoor fan motor heat.

3Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.