Design Flexibility

The VRV IV W series can meet various air conditioning needs by taking full advantage of the characteristics of a water cooled system.

Adaptable to high-rise buildings due to easy installation on each floor

Compact outside units can be easily installed in the machine rooms on each floor. This helps overcome the restriction on differences in height of refrigerant piping. Individual air conditioning can be easily provided in high-rise buildings using this VRV system.

Easy to install in underground shopping malls and subway systems

Individual air conditioning can be easily provided in underground shopping malls, subway systems, etc. using this VRV system because heat exchanging with outdoor air is not required.

Also recommended for condominiums and detached houses

We offer an extensive lineup of small capacity outside units as well as connectable residential indoor units for detached houses. Compact outside units can be installed indoors.

Renovation of an Air Conditioning System

Rising problems for old, conventional water system

Why is renovation necessary?

  1. As equipment ages, its air conditioning capacity weakens with each passing year.
  2. With frequent breakdowns in the outside unit, normal use of air conditioners is unachievable.
  3. The maintenance cost for the equipment keeps rising.
  4. The longer the equipment serves, its noise becomes louder.
  5. Scale formed in water pipes is hard to clean, accelerating corrosion and aging processes.
  6. Meeting the requirements of a 24-hour running IT room is out of the question.
  7. Catering to new tenants’ partitioning changes in a timely manner is difficult.
  8. Charging by household is not possible.
  9. Serving tenants working overtime is difficult.
  10. Central control and management costs too much.
Troublesome issues in renovation?

A Flexible System, Convenient for Expansion/Renovation

Problems with existing water systems can be solved with minimal construction work.

 

1. Indoor installation solves the puzzle of proper placement of outdoor units

The outside units of the water cooled VRV IV W series don’t have necessity to direct heat exchanging with outdoor air. This feature makes it possible to place the outside unit inside the building, which greatly extends design flexibility and makes it easier to adapt to different types of buildings and open to various kinds of creative building exteriors.

2. Part of the old system can be retained for cost reduction

The water cooled VRV IV W series can retain the cooling tower of the old system during renovation, effectively keeping costs down.

3. The compact outside units facilitate the renovation process and saves space for the outside unit area

The outside units of the water cooled VRV IV W series are conveniently compact, which not only enables transport by elevator possible, but also effectively simplifies installation. This also saves a great deal of time and labor.

The modular design featured by the water cooled VRV IV W series enables a free and flexible configuration of the outside units. Outside units can be arranged with one on top of another, saving space for other purposes.

Specifications

Outside Unit

Cooling Only

MODEL RWEYQ6TYM RWEYQ8TYM RWEYQ10TYM RWEYQ12TYM
Combination units
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Cooling capacity kcal/h 13,800 19,300 24,100 28,800
Btu/h 54,600 76,400 95,500 114,000
kW 16.0 22.4 28.0 33.5
Power consumption kW 2.58 3.86 5.43 7.33
Casing colour Ivory white (5Y7.5/1)
Dimensions (H×W×D) mm 1,000 × 780 × 550
Compressor Type Hermetically sealed scroll type
Motor output kW 1.9 2.8 3.7 4.7
Refrigerant piping
connections
Liquid mm φ 9.5 (Flare) φ 12.7 (Flare)
Suction gas *1 mm φ 19.1 (Brazing) φ 22.2 (Brazing)
High and low pressure gas mm φ 19.1 (Brazing) *2 φ 22.2 (Brazing) *2
Water piping
connections
Water inlet PT1 1/4B internal thread
Water outlet PT1 1/4B internal thread
Drain outlet PS1/2B internal thread
Machine weight (Operating weight) kg 146 (148) 147 (149)
Sound level dB(A) 49 50 51 53
Operation range (Inlet water temp.) °C 10 to 45
Capacity control % 23-100 19-100
Refrigerant Type R-410A
Charge kg 3.5 4.2

MODEL RWEYQ26TYM RWEYQ28TYM RWEYQ30TYM
Combination units RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM
RWEYQ10TYM RWEYQ10TYM RWEYQ10TYM
RWEYQ10TYM RWEYQ10TYM RWEYQ10TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Cooling capacity Btu/h 248,000 268,000 287,000
kW 72.8 78.4 84.0
Heating capacity Btu/h 278,000 300,000 322,000
kW 81.5 88.0 94.5
Power consumption Cooling
kW
13.2 14.7 16.3
Heating
kW
13.6 15.2 16.8
Casing colour Ivory white (5Y7.5/1)
Dimensions (H × W × D) mm (1,000 × 780 × 550) × 3
Compressor Type Hermetically sealed scroll type
Motor output kW 2.8 × 2 + 3.7 2.8 + 3.7 × 2 3.7 × 3
Refrigerant piping
connections
Liquid mm ϕ19.1 (Flare)
Suction gas *1 ϕ34.9 (Brazing)
High and low pressure gas ϕ28.6*2, ϕ34.9*3 (Brazing)
Water piping
connections
Water inlet (PT1 1/4B) × 3 internal thread
Water outlet (PT1 1/4B) × 3 internal thread
Drain outlet (PS1/2B) × 3 internal thread
Machine weight (Operating weight) kg 146 × 2 + 147 (148 × 2 + 149) 146 + 147 × 2 (148 + 149 × 2) 147 × 3 (149 × 3)
Sound level dB(A) 55 56
Operation range (Inlet water temp.) °C 10 to 45
Capacity control % 21-100 20-100 19-100
Refrigerant Type R-410A
Charge kg 3.5 + 3.5 + 4.2 3.5 + 4.2 + 4.2 4.2 + 4.2 + 4.2
MODEL RWEYQ14TYM RWEYQ16TYM RWEYQ18TYM RWEYQ20TYM RWEYQ22TYM RWEYQ24TYM
Combination units RWEYQ6TYM RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM
RWEYQ8TYM RWEYQ8TYM RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM RWEYQ12TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Cooling capacity Btu/h 131,000 153,000 172,000 191,000 210,000 229,000
kW 38.4 44.8 50.4 56.0 61.5 67.0
Heating capacity Btu/h 147,000 171,000 193,000 215,000 235,000 256,000
kW 43.0 50.0 56.5 63.0 69.0 75.0
Power consumption Cooling
kW
6.44 7.72 9.29 10.9 12.8 14.7
Heating
kW
6.67 7.96 9.58 11.2 13.5 15.7
Casing colour Ivory white (5Y7.5/1)
Dimensions (H × W × D) mm (1,000 × 780 × 550) × 2
Compressor Type Hermetically sealed scroll type
Motor output kW 1.9 + 2.8 2.8 × 2 2.8 + 3.7 3.7 × 2 3.7 + 4.7 4.7 × 2
Refrigerant piping
connections
Liquid mm ϕ12.7 (Flare) ϕ15.9 (Flare) ϕ19.1 (Flare)
Suction gas *1 mm ϕ28.6 (Brazing)
High and low pressure gas mm ϕ22.2*2, ϕ28.6*3 (Brazing)
Water piping
connections
Water inlet (PT1 1/4B) × 2 internal thread
Water outlet (PT1 1/4B) × 2 internal thread
Drain outlet (PS1/2B) × 2 internal thread
Machine weight (Operating weight) kg 146 × 2 (148 × 2) 146 + 147 (148 + 149) 147 × 2 (149 × 2)
Sound level dB(A) 53 54 55 56
Operation range (Inlet water temp.) °C 10 to 45
Capacity control % 23-100 20-100 19-100
Refrigerant Type R-410A
Charge kg 3.5 + 3.5 3.5 + 4.2 4.2 + 4.2

MODEL RWEYQ32TYM RWEYQ34TYM RWEYQ36TYM
Combination units RWEYQ10TYM RWEYQ10TYM RWEYQ12TYM
RWEYQ10TYM RWEYQ12TYM RWEYQ12TYM
RWEYQ12TYM RWEYQ12TYM RWEYQ12TYM
Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
Cooling capacity Btu/h 305,000 324,000 345,000
kW 89.5 95.0 101
Heating capacity Btu/h 345,000 365,000 386,000
kW 101 107 113
Power consumption Cooling
kW
18.2 20.1 22.0
Heating
kW
19.1 21.3 23.6
Casing colour Ivory white (5Y7.5/1)
Dimensions (H × W × D) mm (1,000 × 780 × 550) × 3
Compressor Type Hermetically sealed scroll type
Motor output kW 3.7 × 2 + 4.7 3.7 + 4.7 × 2 4.7 × 3
Refrigerant piping
connections
Liquid mm ϕ19.1 (Flare)
Suction gas *1 mm ϕ34.9 (Brazing)
High and low pressure gas mm ϕ28.6*2, ϕ34.9*3 (Brazing)
Water piping
connections
Water inlet (PT1 1/4B) × 3 internal thread
Water outlet (PT1 1/4B) × 3 internal thread
Drain outlet (PS1/2B) × 3 internal thread
Machine weight (Operating weight) kg 147 × 3 (149 × 3)
Sound level dB(A) 57 58
Operation range (Inlet water temp.) °C 10 to 45
Capacity control % 19-100
Refrigerant Type R-410A
Charge kg 4.2 + 4.2 + 4.2